Maxpower-corp R.A.S.E.R. HD Manual de usuario Pagina 2

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 2
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 1
Product Features
Built-in closed loop cooling
can support high temperature
water and IT loads from 20 to
80 kW
Fully redundant cooling
system configuration with
self-adjusting valves, requires
only a mechanical hookup
Accepts low and high
temperature cooling water
Hot swappable and field
upgradable Heat eXchanger
(HX) units can support
multiple configurations
Hot swappable and alarmed
fan assemblies assure
continuous operations
Indoor/ Outdoor NEMA 4
enclosure provides superior
strength and protects
equipment from the elements
Shock and vibration isolation
Industry standard 19” wide x
42” deep racks are fully
adjustable
Built-in environmental
monitoring with optional IP
control and GUI interface
Options
EMI Shielding
Stand alone programmable
encrypted security system
with audit trail
16R insulation/fire protection
Fire protection using Novec
1230
Smart power distribution units
with outlet switching and
power monitoring
The R.A.S.E.R. HD is available with blue or black powder coating.
Technical Specifications:
Dimensions.......................................................89” tall x 47” wide x 64” long
Weight………………………………………………………….....2000-2300 lbs*
Dynamic Load Capacity……………………………………….……….2000 lbs
Operational Temperature……………………………………...-40 to 130˚ F*
High Density Equipment Capacity…………...…………..……...……...42U
Total Equipment Capacity…………………………………………20 to 80 kW*
Heat Exchangers Available………………………………...……Single 20 kW
………………………………...Single 40 kW
…………………………… ...……..Dual 20 kW
……………………………….…….Dual 40 kW
Water Connections Per Heat Exchanger………………….…..Inlet 1½” NPT
…….……………...Outlet 1½” NPT
...………....Condensate ½” NPT
Heat Exchanger Water Flow Per Unit……………………..20 kW-12.5 GPM
…………….……...….40 kW-19 GPM
Internal Air Flow Per Heat Exchange……………………..20 kW-1750 CFM
...............................40 kW-2350 CFM
Water supply temperature………………………………………….43 to 90˚ F
All Capacity Ratings Based on 43˚ F Water Supply
* depending upon upgrade options selected
A/C Power Options:
Standard 208-230 VAC 50/60 Hz 20 kW-700 WATTS 40 kW-1200 WATTS
Optional 48 VDC 20 kW-624 WATTS 40 kW-1152 WATTS
230 Yuma St, Denver, CO 80223
Tel (877) 853-8338
www.maxpowercorp.com
Vista de pagina 1
1 2